Cortec-Middle-East-logo-notaglineCortec-Middle-East-logo-notaglineCortec-Middle-East-logo-notaglineCortec-Middle-East-logo-notagline
  • ABOUT US
    • VpCI® Technology
    • MCI® Technology
    • The Cortec® Story
    • Engineering and Field Service
    • Cortec® R&D
    • Asset Integrity Assurance
  • INDUSTRIES
    • Oil & Gas
      • Aboveground Storage Tanks
      • Equipment Preservation
      • Hydrotesting and Mothballing
      • Mothballing
      • Cased Pipeline Crossings
      • Rig Stacking
    • Manufacturing Industries
    • Construction
      • Reinforced Concrete Structures
      • Post-Tensioned Structures
      • Concrete Repair
    • Power & Water
      • Above-ground Storage Tanks
      • Equipment Preservation
      • Hydrotesting and Mothballing
      • Mothballing
      • Cased Pipeline Crossings
    • Aviation
  • PRODUCTS
    • All Purpose Lubricant
    • Surface Preparation
    • Rust Preventives
    • VpCI® Powder
    • VpCI® Additives
    • VpCI® Packaging
    • VpCI® Emitters
    • MCI® for Concrete
  • CONTACT US
Home  »  case studies   »   Reem Island
Published by Cortec Middle East on December 11, 2019
Categories
  • case studies
Tags
Reem Island

Reem Island

Reem Island District Cooling System Preservation with VpCI®-649 BD

Overview

District cooling system preservation became essential at Abu Dhabi Reem Island when completed cooling facilities needed to remain idle for up to two years. Reem Island includes more than 100 towers, approximately 1.4 million m² of office space, and 850,000 m² of retail and community facilities.

Four district cooling plants with capacities greater than 1,000 m³ were proposed for the development. However, two plants were completed before the towers they would support were ready. Therefore, the end clients needed an effective mothballing strategy to protect the completed facilities until they could enter service.

The preservation solution needed to provide long-term corrosion protection. At the same time, the clients wanted to minimize inspections, costs, and potential replacement work during the idle period.

Why District Cooling System Preservation Is Important

District cooling plants contain piping and other metallic components that remain vulnerable to corrosion when the systems sit idle.

Furthermore, the Reem Island cooling systems contained both ferrous and non-ferrous lines. Therefore, the district cooling system preservation strategy needed to protect different metals throughout the mothballing period.

Without suitable preservation, corrosion may increase maintenance requirements before commissioning. A well-planned wet lay-up strategy can help protect the system while reducing the need for frequent intervention.

Application

The project team proposed Cortec® VpCI® technology as an environmentally friendly and cost-effective solution for the Reem Island facilities.

The client accepted VpCI®-649 BD for the wet lay-up preservation program. The team used the product at a 0.4% dosage to achieve the required 24 months of corrosion protection.

In total, the project required approximately 2,970 gallons, equal to 164 drums, of VpCI®-649 BD.

As a result, the team could preserve the completed cooling infrastructure while the associated towers remained under development.

For other industrial corrosion protection solutions, explore the Cortec® Middle East product range.

Why VpCI®-649 BD Was Chosen

Long-Term Corrosion Protection
The project required up to two years of preservation. Therefore, the team used VpCI®-649 BD at a 0.4% dosage to achieve the required 24 months of protection.

Protection for Different Metals
The district cooling network included both ferrous and non-ferrous lines. The selected preservation approach provided protection for these components during the wet lay-up period.

Reduced Inspection Requirements
The customer wanted to minimize inspections while the plants remained idle. Consequently, long-term wet lay-up offered a practical approach for the mothballed facilities.

Cost-Effective Preservation
The preservation strategy also helped minimize costs and potential replacement requirements compared with the traditional methods considered for the project.

Environmentally Friendly Approach
The project team proposed Cortec® VpCI® technology to meet the requirement for an environmentally friendly and cost-effective corrosion protection solution.

Benefits of District Cooling System Preservation

A planned district cooling system preservation program helps protect completed infrastructure when commissioning or operation cannot begin immediately.

In this project, wet lay-up provided the required long-term protection for the cooling system. Moreover, the preservation strategy addressed both ferrous and non-ferrous lines.

The approach also supported the project’s goal of reducing inspections, costs, and replacement requirements during the two-year mothballing period.

Wet Lay-Up for Long-Term Corrosion Protection

Wet lay-up allowed the project team to preserve the completed district cooling facilities while construction of the associated towers continued.

Instead of leaving the cooling system without dedicated corrosion protection, the team used VpCI®-649 BD at the selected concentration.

Therefore, the facilities could remain mothballed for the required period while maintaining corrosion protection throughout the cooling system.

Conclusion

Tabreed – Cooltech Energy adopted wet lay-up with Cortec® VpCI® technology for the Reem Island district cooling facilities.

The solution delivered long-term preservation against corrosion for both ferrous and non-ferrous lines. Furthermore, the approach helped minimize inspections, costs, and potential replacement requirements during the shutdown period.

As a result, the district cooling system preservation strategy provided a practical and cost-effective solution for protecting critical infrastructure for up to 24 months.

Why This Case Matters for District Cooling Operators

  • Completed district cooling plants may require preservation when associated developments face construction or commissioning delays.
  • Wet lay-up offers a practical method for long-term corrosion protection.
  • Both ferrous and non-ferrous system components require suitable protection.
  • A planned preservation strategy can reduce inspection requirements.
  • Effective mothballing can help limit corrosion-related costs and potential replacement work.
  • VpCI® technology provided the required 24-month preservation period in this project.

Frequently Asked Questions

What is district cooling system preservation?
District cooling system preservation protects idle cooling infrastructure against corrosion during shutdowns, mothballing periods, or project delays.

What is wet lay-up preservation?
Wet lay-up keeps a system under treated wet conditions during an idle period to provide corrosion protection for internal metal surfaces.

Why was VpCI®-649 BD selected for the Reem Island project?
The project team selected VpCI®-649 BD to provide long-term corrosion protection while supporting the requirement for an environmentally friendly and cost-effective preservation solution.

How long did the Reem Island district cooling systems require protection?
The end clients required preservation for up to 24 months.

What dosage of VpCI®-649 BD did the project use?
The team used a dosage of 0.4% to achieve the required 24 months of protection.

How much VpCI®-649 BD did the project require?
The project required approximately 2,970 gallons, equal to 164 drums.

Can wet lay-up protect different metals?
In this project, the wet lay-up strategy provided corrosion protection for both ferrous and non-ferrous lines within the district cooling system.

Key Takeaways

  • Reem Island required district cooling system preservation for completed facilities that were not yet ready for operation.
  • The end clients needed to mothball the facilities for up to two years.
  • The project team selected VpCI®-649 BD for wet lay-up preservation.
  • The team applied VpCI®-649 BD at a 0.4% dosage.
  • The solution provided 24 months of corrosion protection.
  • The project required approximately 2,970 gallons, equal to 164 drums.
  • The preservation strategy protected ferrous and non-ferrous lines.
  • Wet lay-up helped minimize inspection, cost, and replacement requirements.

Project Partners

Distributor: Kanoo Group

Clients: Tamouh, Reem Investments, and Aldar Properties

Cortec® Product Used

  • VpCI®-649 BD
Contact Us
Share
0
Cortec Middle East

Related posts

High Rise Building Restoration

High Rise Building Restoration

September 23, 2025

High Rise Building Restoration


Read more
Protection of Electrical Cabinets

Protection of Electrical Cabinets

September 23, 2025

Protection of Electrical Cabinets


Read more
Cleaning and Preservation of Spare Parts

Cleaning and Preservation of Spare Parts

August 24, 2025

Cleaning and Preservation of Spare Parts


Read more

Comments are closed.

Cortec Middle East-logo

QUICK LINKS

  • → HOME
  • → ABOUT US
  • → INDUSTRIES
  • → PRODUCTS
  • → CAREER
  • → CONTACT US
  • → PRIVACY
  • → MEDIA

REQUEST A WEBINAR

REQUEST NOW

SOCIAL MEDIA

ADDRESS

CORTEC® MIDDLE EAST,
2411 Tower B, Jafza One,
Jebel Ali Freezone, DUBAI,
UNITED ARAB EMIRATES


TEL. +971 4 434 0669
FAX. +971 4 434 0668
INQUIRIES@CORTEC-ME.COM

Copyright Cortec® Middle East.
All rights reserved. Cortec®, MCI®, VpCI® 126-Blue®, EcoFilm®, EcoWorks®, Rawn® and Bull Frog® are registered trademarks of Cortec® Corporation.
    • No translations available for this page

      REQUEST A FREE SAMPLE



        Download Layup Manuals

          Select Manual* :


          Offshore Rig Layup PR




            Layup of Land Based Drilling Rigs PR




              Request a Quote


                Talk To Our Experts


                  Subscribe Now

                    Apply Now

                      Upload Your CV